A multiparameter controller/transmitter for measuring level, flow and temperature in open channels with hydraulic restrictions such as flumes or weirs. Supports ultrasonic, radar and piezometric sensors; temperature measurement is available only with ultrasonic sensors.

  • Features:
    • Connection of up to 8 digital sensors with plug-and-play recognition.
    • Integrated 64 Mbit data logger storing up to 250,000 records.
    • Graphical colour TFT display (480x272) for simultaneous measurement display.
    • Interfaces: 4–20 mA, Modbus RTU (RS485), optional Modbus TCP/IP (Ethernet).
    • Four relay outputs for threshold control and one relay for fault signalling.
    • Supports rectangular, trapezoidal and V-notch weirs, and Venturi, Parshall and Palmer Bowlus flumes, among others.
    • Up to 30-point table calibration for non-linear functions.
  • Applications: Pump monitoring and control in sewer systems, irrigation channels, wastewater and industrial processes.